Power Calculator

Calculate watts, kW, kVA, kVAR, amps, power factor, three-phase loads, energy cost, and capacitor bank sizing with NEC Article 220 checks.

4.96 ★ Verified Ratings
232K+ Active Users
v4.3.0 Latest Version
17.5 MB Lightweight APK
Zero Cloud 100% On-Device
Professional Power & Energy Suite

Key Features & Calculation Capabilities

A complete electrical power and energy estimation toolkit engineered for electricians, electrical engineers, energy auditors, and facility managers who need fast, accurate power, load, and cost calculations in the field or office.

Core Calculations

Single-Phase & DC Power Calculator

Solve for watts, kW, amps, volts, or power factor from any two known values. Core relations: P = V × I × PF, I = P ÷ (V × PF), and kW = (V × I × PF) ÷ 1,000. Supports DC, single-phase AC, and resistive loads with power factor correction.

W / kW / Amps DC & Single-Phase
Three-Phase

Three-Phase kW, kVA & Amps

Calculate balanced three-phase real power, apparent power, and line current with the √3 factor. Formulas: kW = (√3 × VLL × I × PF) ÷ 1,000, kVA = (√3 × VLL × I) ÷ 1,000, and Amps = (kVA × 1,000) ÷ (√3 × VLL). Supports line-to-line and line-to-neutral inputs.

√3 × V × I × PF LL & LN
Power Factor

Power Factor, kVAR & Phase Angle

Compute power factor from kW and kVA (PF = kW ÷ kVA), derive reactive power kVAR = √(kVA² − kW²), and convert between PF and phase angle with PF = cos θ. Flags low power factor below 0.90 and estimates penalty exposure where utilities charge PF penalties.

PF / kVAR / θ Low PF Warning
Correction

Capacitor Bank Sizing Calculator

Size power factor correction capacitors with kVARcap = kW × (tan θ₁ − tan θ₂), where θ₁ is the existing phase angle and θ₂ is the target. Example: a 150 kW load corrected from 0.80 to 0.95 PF needs about 57 kVAR. Includes correction factor lookup tables and capacitor current estimation.

kVARcap PF Correction
Energy Cost

Energy Consumption & Cost Planner

Estimate daily, monthly, and annual energy use with kWh = (Watts × Hours) ÷ 1,000, then multiply by the local tariff for cost. Run appliance-level scenarios, compare load profiles, and calculate simple payback for efficiency upgrades such as LED retrofits, PF correction, and motor replacements.

kWh / Tariff Payback Period
Compliance

NEC Load Checks, Reports & Export

Cross-check connected loads against NEC Article 220 general lighting densities (3 VA/ft² for dwellings), demand factors, and the 2026 Article 120 relocation updates. Generate PDF calculation sheets showing inputs, formulas, results, and NEC references, and export to CSV for project files. All calculations run offline.

NEC Art. 220 / 120 PDF / CSV Export