Electrical Calculator

Calculate Ohm's Law, power, voltage drop, wire size, breaker size, conduit fill, motor FLC, energy consumption, and cost with NEC code checks.

4.96 ★ Verified Ratings
215K+ Active Users
v4.1.0 Latest Version
18.2 MB Lightweight APK
Zero Cloud 100% On-Device
Professional Electrical Suite

Key Features & Calculation Capabilities

A complete electrical engineering toolkit engineered for electricians, engineers, contractors, and students who need fast, accurate circuit calculations, code checks, and cost projections in the field or the classroom.

Core Calculations

Ohm's Law & Power Calculator

Solve for voltage, current, resistance, or power from any two known values. The core relations are V = I × R, P = V × I, P = I² × R, and P = V² ÷ R. Supports DC and single-phase AC, with power factor input for true power calculations.

V / I / R / P DC & AC
Wiring

Voltage Drop & Wire Size Selector

Calculate voltage drop with VD = (2 × K × I × L) ÷ CMA for single-phase and VD = (√3 × K × I × L) ÷ CMA for three-phase. K is 12.9 for copper and 21.2 for aluminum. The app then selects the smallest AWG or kcmil conductor that keeps drop within the target percentage and satisfies NEC 310.16 ampacity.

Copper / Aluminum NEC 310.16
Protection

Breaker Sizing & Load Calculator

Size overcurrent protection with the NEC continuous load rule: Idesign = 1.25 × Icontinuous + Inon-continuous. Then select from NEC 240.6 standard breaker sizes: 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125 A and upward. The next standard size up rule applies for conductors 8 AWG and larger.

125% Continuous NEC 240.6
Raceways

Conduit Fill & Motor FLC

Check conduit fill against NEC Chapter 9, Table 1 limits: 53% for one conductor, 31% for two, and 40% for three or more. For motors, use NEC Table 430.250 full-load current values, then apply the 125% continuous-duty factor for branch-circuit conductors and overcurrent protection.

53 / 31 / 40% Fill NEC 430.250
Energy

Energy Consumption & Cost Planner

Estimate daily, monthly, and annual energy use with kWh = (Watts × Hours) ÷ 1,000, then multiply by the local tariff for cost. Run appliance-level scenarios and compare LED, HVAC, or motor upgrade payback periods. Includes a simple payback calculator for efficiency investments.

kWh / Tariff Payback Period