★ Electrical & Engineering Android & iOS

Conduit Fill Calculator

Calculate fill percentage, conductor count, conduit sizing, jam ratio, and NEC Chapter 9 compliance for EMT, PVC, RMC, and IMC.

4.95 ★ Verified Ratings
198K+ Active Users
v3.8.0 Latest Version
16.8 MB Lightweight APK
Zero Cloud 100% On-Device
Professional Conduit Fill Suite

Key Features & Calculation Capabilities

A complete conduit fill and raceway sizing toolkit engineered for electricians, electrical engineers, contractors, and inspectors who need fast, accurate NEC Chapter 9 compliance checks in the field or office.

Core Calculation

Fill Percentage & Conductor Area

Calculate conduit fill from total conductor area divided by conduit internal area. Fill % = (Sum of Conductor Areas ÷ Conduit Internal Area) × 100. Compare against NEC Chapter 9, Table 1 limits: 53% for one conductor, 31% for two, and 40% for three or more.

Fill % 53 / 31 / 40%
Conduit Types

EMT, PVC, RMC & IMC Support

Look up internal area from NEC Chapter 9, Table 4 for EMT, PVC Schedule 40, PVC Schedule 80, RMC, and IMC from 1/2" through 4". For example, 1/2" EMT has 0.304 in² internal area, while 1/2" PVC Sch 40 has 0.285 in² and PVC Sch 80 has 0.242 in².

EMT / PVC / RMC / IMC 1/2" – 4"
Sizing

Minimum Conduit Size Recommendation

When fill exceeds the NEC limit, the app recommends the next larger trade size. It also checks the 60% nipple allowance for conduits 24 inches or shorter, and flags when a custom or non-standard size is required.

Auto Step-Up 60% Nipple
Jam Ratio

Jam Ratio & Pulling Risk Analysis

Jam Ratio = Conduit ID ÷ Conductor OD. A ratio between 2.8 and 3.2 signals a high risk of conductors wedging into a triangular formation and locking during pulling. The app warns on risky combinations and suggests an alternative conduit size or conductor arrangement.

2.8–3.2 Risk Zone Pull Safety
Conductors

THHN, XHHW & Multi-Conductor Support

Uses NEC Chapter 9, Table 5 conductor areas for THHN/THWN-2, XHHW, and other common insulation types. Also supports multi-conductor cables treated as a single conductor for fill calculations, and elliptical cables sized by their major diameter.

THHN / XHHW Multi-Conductor
Reporting

Reports, NEC References & Export

Generate PDF calculation sheets showing conduit type, trade size, conductor list, total area, fill percentage, pass/fail status, and the applicable NEC Chapter 9 table references. Export to CSV for project documentation. All calculations run offline on-device.

PDF / CSV Export Offline Reports