Cable Size Calculator

Calculate conductor ampacity, voltage drop, derating factors, NEC vs IEC sizing, and solar PV cable requirements with professional precision.

4.96 ★ Verified Ratings
245K+ Active Users
v4.5.0 Latest Version
19.1 MB Lightweight APK
Zero Cloud 100% On-Device
Professional Cable Sizing Suite

Key Features & Calculation Capabilities

A complete cable sizing and verification toolkit engineered for electricians, electrical engineers, solar installers, and project designers who need fast, accurate ampacity, voltage drop, and derating calculations across NEC and IEC standards.

Core Calculation

Ampacity & Conductor Sizing

Calculate the minimum conductor size from design current and installation method. The app applies NEC 310.16 allowable ampacities for copper and aluminum at 60°C, 75°C, and 90°C, and IEC 60364-5-52 Table B.52.2–B.52.5 base ratings for PVC and XLPE insulation.

NEC 310.16 IEC 60364-5-52
Voltage Drop

Voltage Drop & Run Length Calculator

Calculate voltage drop using ΔV = (2 × L × I × ρ) ÷ A for single-phase and ΔV = (√3 × L × I × ρ) ÷ A for three-phase, where ρ is 0.0172 Ω·mm²/m for copper and 0.0282 Ω·mm²/m for aluminum. The app flags designs exceeding NEC's 2%/1% split or IEC 62548's 3% total limit.

Single / Three-Phase NEC vs IEC Limits
Derating

Temperature, Grouping & Soil Correction

Apply combined derating factors k = k₁ × k₂ × k₃ from IEC 60364-5-52 Tables B.52.14–B.52.21. Temperature correction at 45°C gives 0.87 for XLPE and 0.79 for PVC; grouping of four circuits in conduit reduces ampacity by 20%; soil thermal resistivity above 2.5 K·m/W further reduces buried cable ratings.

k₁ × k₂ × k₃ IEC Correction Tables
NEC vs IEC

Dual-Standard AWG & mm² Sizing

Switch between NEC (AWG/kcmil, Imperial) and IEC (mm², Metric) sizing in one tap. Both calculations follow the same methodology — design current, protective device rating, installation method, derating, and voltage drop — but use the correct tables, reference temperatures, and safety margins for each jurisdiction.

AWG / kcmil mm² / Metric
Solar PV

NEC 690.8 Solar Cable Sizing

Apply the correct two-step 156% multiplier (1.25 × 1.25) for PV source circuits, as required by NEC 690.8. Size DC conductors for ≤2% voltage drop and AC output conductors for ≤3%, then confirm conductor ampacity after rooftop temperature derating. Common results: 10 AWG residential strings, 8 AWG commercial strings, 4/0 AWG main feeders.

156% Isc NEC 690.8
Reporting

Reports, Standards & Export

Generate PDF calculation sheets showing design current, selected conductor, derated ampacity, voltage drop, pass/fail status, and the applicable NEC or IEC table references. Export to CSV for project files. All calculations run on-device and work fully offline.